Parameters - Honeywell Krom Schroder BCU 580 Technical Information

Burner control unit
Table of Contents

Advertisement

Parameters

10 Parameters
Any changes to parameters will be saved to the parameter chip card.
Name
Burner 1 FS1 flame signal switch-off
threshold
Burner 2 flame signal switch-off
threshold FS2
Flame control
High temperature operation
Burner 1 start-up attempts
Burner 2 start-up attempts
Restart
Safety time during operation
BCU 580 · Edition 11.15l
Parameter
Value range
01
0 – 20
02
0 – 20
0
1
2
3
04
4
5
6
7
8
0
06
2
3
1
07
2
3
1
08
2
3
0
1
2
09
3
4
5
6
19
0; 1; 2
Description
Burner 1 FS1 flame signal switch-off threshold in µA
Burner 2 FS2 flame signal switch-off threshold in µA
Ionization
UVS
UVD
Ionization1 and UVS 2
Ionization1 and UVD 2
UVS 1 and ionization 2
UVD 1 and UVD 2
UVD 1 and ionization 2
UVD 1 and UVS 2
Off
Intermittent operation with UVS
Continuous operation with ionization/UVD
1 start-up attempt
2 start-up attempts
3 start-up attempts
1 start-up attempt
2 start-up attempts
3 start-up attempts
Off
Burner 1
Burner 2
Burner 1 and burner 2
Max. 5 × in 15 min. for burner 1
Max. 5 × in 15 min. for burner 2
Max. 5 × in 15 min. for burner 1 and burner 2
Time in seconds
Factory default
settings
2
(5 when P04 = 1)
2
(5 when P04 = 1)
0
0
1
1
0
1
54