Parameters

4 Parameters
Description
Flame signal, pilot burner
Flame signal, main burner
Program status when the most recent fault occurred
Switch-off threshold, pilot burner
Switch-off threshold, main burner
Start-up attempts, pilot burner**
Start-up attempts, main burner**
Restart, pilot burner
Restart, main burner
Safety time during operation for V1 and V2 t
Flame simulation check in start-up position/standby
Permanent pilot burner
Minimum burner on time t
B
Minimum burner pause time t
BP
Pilot burner safety time on start-up t
Pilot burner flame proving period t
Main burner safety time on start-up t
Main burner flame proving period t
Air valve control
Air valve can be activated externally on start-up
Air valve closed/can be activated in the event of malfunction
BCU 480 · Edition 03.16l
SB
**
SA1
FS1
**
SA2
FS2
Parameter
Value range
01
0 – 99 μA
02
0 – 99 μA
03
x0 – x8
04
1 – 20 µA
05
1 – 20 µA
10
1 – 4
11
1 – 4
12
0; 1
13
0; 1
14
1; 2 s
15
0; 1
16
0; 1
20
25 s
21
0 – 250 s
22
3; 5; 10 s
23
0 – 25 s
24
3; 5 s
25
0 – 25 s
30
0; 1; 2; 3
31
0; 1
32
0; 1
Factory
Adjustable*
default setting
1 µA
1 µA
1
1
0
0
1 s
1
1
t
SA
0 s
0 s
0 s
0
0
1
29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents