Function Of Terminal 66; Function Of Terminal 67; Function Of Terminal 68 - Honeywell Krom Schroder BCU 580 Technical Information

Burner control unit
Table of Contents

Advertisement

Parameters

10 .10 .4 Function of terminal 66

Parameter 71
Parameter 71 = 0: Off.
Parameter 71 = 8: AND with input at terminal 46 (emer-
gency stop).
Parameter 71 = 20: LDS ignition position check.
The BCU does not perform a burner start-up, restart or
start-up attempt until the butterfly valve is in ignition
position. To ensure that the burners only start with the
start-up fuel rate, the FCU issues an enable signal to
start the burner via terminal 66 to the BCU with setting
P71 = 20. In addition, the safety interlocks must have
been enabled by the FCU.
FCU
µC
53
53
54 55
54 55
M
M
BCU 580 · Edition 11.15l
L1 L1
+24V
66
66
BCU
BCU

10 .10 .5 Function of terminal 67

Parameter 72
Parameter 72 = 0: Off.
Parameter 72 = 8: AND with input at terminal 46 (emer-
gency stop).

10 .10 .6 Function of terminal 68

Parameter 73
Parameter 73 = 0: Off.
Parameter 73 = 8: AND with input at terminal 46 (emer-
gency stop).
101