Honeywell Krom Schroder BCU 580 Technical Information page 57

Burner control unit
Table of Contents

Advertisement

Parameters
Name
Capacity control (bus)
Password
Burner application
Pilot burner
Fieldbus communication
Safety time 1 tSA1
Flame proving period 1 tFS1
Safety time 2 tSA2
Flame proving period 2 tFS2
BCU 580 · Edition 11.15l
Parameter
Value range
0
1
2
3
75
4
5
77
0000 – 9999
0
1
2
78
3
4
5
0
79
1
0
80
1
2
94
2, 3, 5, 10
95
0 – 20
96
2, 3, 5, 10
97
0 – 20
Description
Off
MIN. to MAX. capacity; standby in position for MIN.
capacity
MIN. to MAX. capacity; standby in CLOSED position
IGNITION to MAX. capacity; standby in CLOSED
position
MIN. to MAX. capacity; standby in position for MIN.
capacity; burner quick start
IGNITION to MAX. capacity; standby in CLOSED position;
burner quick start
Four-digit number code
Burner 1
Burner 1 with pilot gas
Burner 1 and burner 2
Burner 1 and burner 2 with pilot gas
Two-stage burner 1
Burner 1 and two-stage burner 2
With shut-down
In continuous operation
Off
With address check
No address check
Time in seconds
Time in seconds
Time in seconds
Time in seconds
Factory default
settings
0
1234
2
0
1
5
2
5
2
57

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents