Honeywell Krom Schroder BCU 580 Technical Information page 47

Burner control unit
Table of Contents

Advertisement

Profinet
"BCU input terminal information" module (device ➔
controller) – slot 9
This module transfers the signal states of the digital in-
puts on the BCU (input terminals) to the PLC.
Bit Byte n
Byte n+1
0
Terminal 1
Terminal 48
1
Terminal 2
Terminal 49
2
Terminal 3
Terminal 50
3
Free
Terminal 51
4
Terminal 44
Terminal 52
5
Terminal 45
Terminal 65
6
Terminal 46
Terminal 66
7
Terminal 47
Terminal 67
"BCU output terminal information" module (device ➔
controller) – slot 10
This module transfers the signal states of the digital
outputs on the BCU (output terminals) to the PLC.
Bit Byte n
0
Terminal 9
1
Terminal 10
2
Terminal 13
3
Terminal 14
4
Terminal 15
5
Terminal 17/18
6
Terminal 37/38
7
Terminal 41
1)
Only for BCU..F2: terminal 53 is used as an input.
Bit 6 has no function.
BCU 580 · Edition 11.15l
Byte n+2
Format
Terminal 68
BOOL
Free
BOOL
Free
BOOL
Free
BOOL
Free
BOOL
Free
BOOL
Free
BOOL
Free
BOOL
Byte n+1
Format
Terminal 42
BOOL
Terminal 43
BOOL
Terminal 53
1)
BOOL
Terminal 54
BOOL
Terminal 55
BOOL
Terminal 56
BOOL
Terminal 57
BOOL
Free
BOOL
47

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents