Alarms
6.5 Example program for program alarms
Creating a text list
To create the text list for the example program, follow these steps:
1. Double-click on the "Text lists" command in the program tree.
The text list editor opens.
2. Double-click "<Add>" in the Text lists area.
A new text list is added.
3. Name the text list "level_textlist".
4. Double-click "<Add>" in the Text list entries area of level_textlist.
A new text list entry is added in the level_textlist text list.
5. Enter the alarm text for the maximum fill level in the "Entry" column.
6. Add another entry in the text list.
7. Enter the alarm text for the minimum fill level in the "Entry" column.
Figure 6-15
Creating a text list
Result: You have created the text list for the alarm text.
94
Function Manual, 11/2019, A5E03735838-AF
Diagnostics