Siemens SIMATIC S7-1500 Function Manual page 42

Diagnostics
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Subordinate "Alarm display" tab
System diagnostics alarms are output in the "Alarm display" tab.
Figure 4-12
"Alarm display" tab
To receive alarms in STEP 7, follow these steps:
1. Open the project view.
2. Select the required CPU in the project tree.
3. To connect online with the respective CPU, select the shortcut menu command "Go
online".
4. Select the required CPU once again in the project tree and select the shortcut menu
command "Receive alarms".
Figure 4-13
5. Alarms are now displayed in the alarm display. "Archive view" is enabled by default.
6. To display the latest alarms, click the "Active alarms" icon
Diagnostics
Function Manual, 11/2019, A5E03735838-AF
Receive alarms
Setting and determining system diagnostics
4.2 Options for displaying system diagnostics
.
41

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents