10. Repeat Steps 5-8 until all the readings are correct with no further adjustments
necessary.
11. Turn power OFF. Set DIP Switch #7 ON (deg. C). Move DVM (+) plus lead to
Signal conditioner connector terminal 11 (terminal 4 for CH-2). Turn power back
ON.
12. Set mV Source as follows, and adjust "Deg. C Lo Pot" for the corresponding
DVM reading. Actual should read the value shown.
Type
J
K
R
13. Set mV Source as follows, and adjust "Deg. C Hi Pot" for the corresponding
DVM reading. Actual should read the value shown.
Type
J
K
R
14. Set mV Source as follows. DVM and Actual Readings should be as shown.
Type
J
K
R
15. Repeat Steps 12-14 until all the readings are correct with no further adjustments
necessary.
16. If calibrating one channel at a time, power-down the Series 1500 and mV Source.
Move the C/J Compensator from the CH-1 connector terminals to the CH-2
terminals, and move the shorting wiring to the CH-1 terminals. Then perform
Steps 6-14 for CH-2.
Field Calibration, Appendix
mV Source
DVM Reading
-0.028VDC ± 0.003
-0.885mV, (0°F)
-0.028VDC ± 0.003
-0.692mV, (0°F)
+0.448VDC ± 0.003
2.282mV, (550°F)
mV Source
DVM Reading
1.100VDC ± 0.003
39.40mV, (1300°F)
2.055VDC ± 0.003
52.93mV, (2400°F)
2.662VDC ± 0.003
20.28mV, (3100°F)
mV Source
DVM Reading
0.4922VDC ± 0.003
17.19mV, (600°F)
1.014VDC ± 0.003
26.97mV, (1200°F)
1.534VDC ± 0.003
10.27mV, (1800°F)
Field Calibration
NOTE
Steps 10-14 only
required if the deg.
C Analog Output
is used.
Actual Reading
- 18°C ± 3
- 18°C ± 3
287°C ± 3
Actual Reading
704°C 3
1315°C ± 3
1704°C ± 3
Actual Reading
315°C ± 3
649°C ± 3
982°C ± 3
WATLOW Series 1500 User's Manual