SYSTEM OPERATING CONTROLS AND COMPONENTS

The unit is furnished with a microprocessor control system. Once the setpoint is entered at the Cab Command, the
unit will operate automatically to maintain the desired temperature within very close limits. See
Beware of unannounced starting of the evaporator or condenser fans. The unit may cycle fans
unexpectedly as control requirements dictate.
Under no circumstances should anyone attempt to repair the microprocessor module or Cab
Command! Should a problem develop with these components, contact your nearest Carrier
Transicold dealer for replacement.
2.6

UNIT SPECIFICATIONS

2.6.1

Compressor Data

2.6.2

Refrigeration System Data

a. Defrost Timer
Automatic triggering or at preset intervals: 0 (Disabled), auto, 1h, 2h, 3h, 4h, 5h, 6h
b. High Pressure Switch (HP1)
Cutout at: 355 psig ± 10 psig; Cut-in at: 290 psig ± 10 psig
c. Condenser Pressure Control Switch (HP2)
Cutout at: 130 psig ± 10 psig; Cut-in at: 175 psig ± 10 psig
d. Refrigerant charge
Refer to
Table
2–1.
62-11848
!
!

Figure 2.6 Cab Command

Model
Displacement
No. Cylinders
Oil Charge
Approved Oil
WARNING
CAUTION
SD 5H09
87cc
5
0.422 pint (200 ml)
Carrier POE #46-60002-02
2-8
Section
3.2.1.