ABB AC 900F Mounting And Installation Instructions Manual page 57

Process automation freelance 2016
Table of Contents

Advertisement

Section 3 Modules
Electrical connection
CP-C MM_electrical connection.png
Terminal assignment
Terminals
M&I – AC 900F Controller
Designation
Function
REMOTE OFF If the terminals are short circuited by a normally
open contact (R < 1 kΩ), for instance, the power
supply unit is switched off remotely.
If the resistance R between the terminals is
> 10 kΩ, the power supply unit is switched on.
Attention:
Terminal potential = Input voltage
INPUT OK
Potential-free change-over contact
message
11-14 closed and 11-12 opened, when the power
supply unit input voltage is > 85 V AC / 90 V DC.
11-12 closed and 11-14 opened, when the power
supply unit input voltage is 82 V AC / 70 V DC.
11-14 also closed with REMOTE OFF.
OUTPUT OK
Potential-free change-over contact
message
21-24 closed and 21-22 opened, when the power
supply unit output voltage is 20.2 V AC / V DC.
21-22 closed and 21-24 opened, when the power
supply unit output voltage is 19.8 V AC / V DC.
CP-C MM messaging module
57

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents