Boot configuration
Before using the display unit for additional settings, access the F3 Display Settings
menu to perfectly adjust the brightness and the contrast of the display.
F1 - IP Address
IP Address setting is mandatory to communicate with the AC 900F via Ethernet.
Press F1 to access the Network submenu.
The IP address of the
the first line (read only). The gateway address can only be changed using the
terminal program.
Specify in the second line whether the controller is used in redundant configuration
or not. This setting must correspond to the hardware structure in Freelance
Engineering. The AC 900FR hardware object requires the Redundancy enabled
setting. Press the arrow key on the right to select the function and the top arrow key
to enable the redundancy mode.
Network_settings.png
To configure an Ethernet interface, press the function key assigned to the relevant
interface. When pressing the F1 key, for instance, the settings of the Eth1 interface
are displayed.
The configuration of [Eth4] is not provided for the PM 901F CPU module.
Change the IP address using the arrow keys. If required, proceed in the same way to
change the subnet mask. Make sure that the interface is enabled, if required. This
process can be interrupted at any time by pressing the ESC key. Press OK to apply
the changed settings.
106
Gwy:000.000.000.000
Section 7 Commissioning
default gateway is displayed in
M&I – AC 900F Controller