CI 773F PROFIBUS-DP Master Interface
Number of slaves
Controller redundancy support Yes
Hot plug
HCIR
LED status displays
After having been switched on, the CI 773 PROFIBUS module performs a self-test
during power-up. During initialization, with newly configured modules or after a
change of the operating mode, all LEDs may light up briefly before reaching the
defined status.
LED
PWR
STA
RUN
LED L
38
Color
Status
Meaning
Green
ON
Module in operation and must not be removed
OFF
Module not in operation and may be removed, if re-
quired
Green
ON
Active module operating properly
OFF
Module start-up
Orange ON
Module identified by the CPU module, but not active
Red
ON
Module error
Green
ON
Module has taken over the PROFIBUS master func-
tion
OFF
Module inactive relative to the PROFIBUS
Green
200 ms
Module ready to take over the master function
pulse
Green
ON
Bus traffic
OFF
No bus traffic