ABB AC 900F Mounting And Installation Instructions Manual page 40

Process automation freelance 2016
Table of Contents

Advertisement

CM 772F PROFIBUS-DP Master Interface
Controller redundancy support No
Hot plug
HCIR
LED status displays
After having been switched on, the CI 772 PROFIBUS module performs a self-test
during power-up. If the test is successfully performed, the yellow LED RDY lights
up, if not, the LED starts to flash and the initialization is aborted. If the LED RDY
does not light up at all, the PROFIBUS module is probably defective. During
initialization, with newly configured modules or after a change of the operating
mode, all LEDs may light up briefly before reaching the defined status.
LED
PWR
RDY
RUN
STA
40
Color
Status
Green
ON
OFF
Yellow
ON
Cyclic flashing
Non-cyclic flashing
OFF
Green
ON
Cyclic flashing
Non-cyclic flashing
OFF
Yellow
ON
OFF
No
No
Meaning
Voltage is applied
No voltage is applied
Coupler ready for operation
Boot loader is active
Hardware or system error
Defective hardware
Communication on
Ready for communication
Parameterization error
No communication
DP master: data or token are transmit-
ted via the network
DP master: No token
Section 3 Modules