Wiring the DC Input Power Source
Figure 83: Torquing the DC Power Supply Terminal Block Plug Screws
1
Torque is from 0.5 Nm (4.425 lbf in. to 0.6 Nm (5.310 lbf in.)
Step 9
Repeat Step 6 through Step 8 for the remaining two DC input power source wires, the positive lead wire and the negative
lead wire (see the following figure).
Figure 84: Inserting the DC Power Supply Terminal Block Plug in the Block Header
1
DC power supply negative (-) lead wire
2
DC power supply positive (+) lead wire
Secure the wires coming in from the terminal block plug so that they cannot be disturbed by casual contact.
Caution
Step 10
Use a tie wrap to secure the wires to the rack, so that the wires are not pulled from the terminal block plug by casual
contact. Make sure the tie wrap allows for some slack in the ground wire as shown in the following figure.
Removing and Replacing FRUs from the Cisco ASR 1000 Series Routers
118
Removing and Replacing FRUs from the Cisco ASR 1000 Series Routers
3
DC power supply ground lead wire