Removal procedure 4.6/5.0/6.0/7.1 kw class

Advertisement

Si001654EA
Step
2
Pull out the electronic
expansion valve coil.
3
Remove the terminal
cover.
4
Remove the protection
bushing.
5
Disconnect the
compressor lead wires
and the overload
protector.
Removal Procedure
Procedure
Protection bushing
Overload
protector
Electronic Expansion Valve Coil / Four Way Valve
Electronic
expansion
valve coil
(R23217)
Terminal cover
(R23218)
U (red)
V (yellow)
W (blue)
(R22244)
Points
For RX(K)M71QVMA, the
wiring of the compressor
lead wires is slightly
different.
V (yellow)
U (red)
W (blue)
(R24119)
17