Removal procedure 4.6/5.0/6.0/7.1 kw class

Advertisement

Si001654EA
Step
4
Disconnect the
connector [S80], pull
out the clamp (1) and
cut the clamp (2).
5
Disconnect the
connector [S40].
6
Disconnect the relay
connector for
compressor and pull out
the clamp.
Removal Procedure
Procedure
[S80]
Clamp (1)
[S40]
Relay connector
Clamp
[S80]: four way valve coil
Clamp (2)
The cooling only models
have no harness for [S80].
The position of the clamp (1)
varies depending on the
model.
Some models do not have
clamp (2).
When reassembling, fit the
clamps back to the hole to
make sure the wires do not
touch the four way valve.
(R23197)
[S40]: overload protector
For RX(K)M71QVMA, make
sure the relay connector for
compressor is under the
electrical box.
(R23198)
Relay connector
When reassembling, fit the
clamp back to the hole to
make sure the wires do not
touch the four way valve
pipe.
Clamp
(R23199)
Wire
Electrical Box
Points
Electrical box
(R24114)
Four way valve pipe
(R24115)