4. Select the "Synchronization via terminal bus (slave)" check box.
5. Select the "Accept time from a connected WinCC server" option button.
6. Click "OK".
5.5.4

How to set time synchronization on an OS in a domain with central time master.

Example configuration
The SICLOCK TC 400 central plant clock is used in a Windows domain for time synchronize
of the OS.
Requirements
● All operator stations must be installed in one domain.
● The SICLOCK TC 400 must be connected to the terminal bus and the plant bus.
● For the CP of the OS server the "Time tracking" option is selected in NetPro.
● The OS server must be equipped with a communication module:
● All automation systems must be configured as time slaves (exceptions: CPU 416-3 PN/DP,
Time synchronization (V8.0)
Function Manual, 03/2012, A5E02779849-02
All associated check boxes and text boxes will then be made available for selection.
– CP 1613 or CP 1623 (more than 8 AS or high-availability AS)
– BCE (up to 8 AS)
CPU 414-3 PN/DP).
Configuring time synchronization
5.5 Configuring the time synchronization of the OS
73