5.9 Configuring time synchronization for the SIMATIC PCS 7 BOX and SIMATIC PCS 7 AS RTX
Synchronizing the SIMATIC PCS 7 BOX or the SIMATIC PCS 7 AS RTX as a single station system
using the PC clock
For a single station system, you need to set the PC clock as the source for time synchronization.
1. Select the menu command PC Based Control > WinAC Time Synchronization in the Start
2. In the "Settings" group under "Source", click "PC Clock".
3. Select the time base ("Time base" option button) according to the type of time display
4. Click "Start" to initiate time synchronization.
5. Click "Close" to close the dialog box.
5.9.3

How to set the OS properties

Introduction
PCS 7 OS and the AS are synchronized via the local PC clock.
Requirements
● WinCC Explorer must be open.
● This procedure is only relevant for the SIMATIC PCS 7 BOX.
Procedure
1. Select the "Computer" object from the tree structure in WinCC Explorer.
2. Select Properties from the shortcut menu.
3. Click "OK".
4. Select the "Properties" tab.
Time synchronization (V8.0)
Function Manual, 03/2012, A5E02779849-02
menu under the Siemens SIMATIC programs.
The "WinAC Time Synchronization" dialog box opens.
required:
– The displayed time should match the local time, including daylight saving changes. A
continuous time should be set on the AS (GMT/UTC):
Time base: GMT
– The time should be displayed uniformly across all levels and functions: Time base: Local
Note: Daylight saving and standard time must be set manually. Please contact Customer
Support regarding automatic switchover.
The "Computer List Properties" dialog box opens.
The "Computer Properties" dialog box opens.
Configuring time synchronization
103