Dip Switch Programming - Whelen Engineering Company IPS 400 Product Manual

In-plant personnel warning system
Table of Contents

Advertisement

Warning Tone Signal/PA Announcement Timing Information
*
Duration is indicated as: Minutes (_) and Seconds (_ _). Unless specified otherwise by a customer, the standard
factory programming is for an event duration of three minutes (3-00), with the exception of the five-second test.
**
NOON TEST is referred to as a 5 SEC WAIL on the front panel of the ESC-864.

7.4 DIP Switch Programming

The ESC-864 controller board has two, eight-position dip switches. The switches are set by the manufacturer in
accordance with the users application and the software/hardware options that are installed into the system at the
time of manufacture. The dip switches control function settings and instant status settings. The Test Sheet, included
with each IPS, refers to these settings as Function Dips (SW 1) and Status Dips (SW 2).
Position
1
2
3
4
5
6
7
8
TONE
SIGNAL
1
WAIL
2
ATTACK
3
ALERT
4
PA
5
AIR HORN
6
HI/LO
7
WHOOP
8
NOON TEST
Function Dips (SW 1) Programming Functions
Function
Not Used
Decoder Format
SI TEST® LED
Warning Signal (Siren) Type
AC Battery Check
Instant Response
Immediate Response
Master XMT
DURATION
__ -- __ __
__ -- __ __
__ -- __ __
__ -- __ __
__ -- __ __
__ -- __ __
__ -- __ __
**
__ -- __ __
Setting/Use
On (10 digit)
Off (8 digit)
On (30 sec clear)/Off (latch)
On (oscillating)
Off (stationary)
On/Off
On/Off
On/Off
On/Off
25
*
Off