To Perform Vacuum Drying; To Insulate The Refrigerant Piping; Charging Refrigerant; About Charging Refrigerant - Daikin LRMEQ3AY1 Installer And User Reference Manual

Air-cooled refrigeration condensing unit
Table of Contents

Advertisement

6.5.5

To perform vacuum drying

NOTICE
The connections to the indoor units and all indoor units
should also be leak and vacuum tested. Keep, if existing,
all (field supplied) field valves to the indoor units open as
well.
To remove all moisture from the system, proceed as follows:
1 Evacuate the system for at least 2 hours to a target vacuum of
–⁠ 1 00.7 kPa (–⁠ 1 .007 bar/5 Torr).
2 Check that, with the vacuum pump turned off, the target
vacuum is maintained for at least 1 hour.
3 Should you fail to reach the target vacuum within 2 hours or
maintain the vacuum for 1 hour, the system may contain too
much moisture. In that case, break the vacuum by pressurising
with nitrogen gas to a gauge pressure of 0.05  MPa (0.5  bar)
and repeat steps 1 to 3 until all moisture has been removed.
4 Depending on whether you want to immediately charge
refrigerant through the refrigerant charge port or first pre-charge
a portion of refrigerant through the liquid line, either open the
outdoor unit stop valves, or keep them closed. See
charge refrigerant" on page 20
INFORMATION
After opening the stop valve, it is possible that the pressure
in the refrigerant piping does NOT increase. This might be
caused by e.g. the closed state of the expansion valve in
the outdoor unit circuit, but does NOT present any problem
for correct operation of the unit.
6.6

To insulate the refrigerant piping

After finishing the leak test and vacuum drying, the piping must be
insulated. Take into account the following points:
▪ Make sure to insulate the connection piping and refrigerant piping
branching entirely.
▪ Be sure to insulate the liquid and gas piping (for all units).
▪ Use heat resistant polyethylene foam which can withstand a
temperature of 70°C for liquid piping and polyethylene foam which
can withstand a temperature of 120°C for gas piping.
▪ Take the following into account when determining the insulation
thickness:
Liquid pipe minimum temperature
Gas pipe minimum temperature
Condensation might form on the surface of the insulation.
▪ If there is a possibility that condensation on the stop valve might
drip down into the indoor unit through gaps in the insulation and
piping because the outdoor unit is located higher than the indoor
unit, this must be prevented by sealing up the connections. See
below figure.
b
a
a
Insulation material
b
Caulking etc.
LRMEQ3+4AY1
Air-cooled refrigeration condensing unit
4P442131-1 – 2016.03
"6.7.4  To
for more information.
20°C
–10°C
6.7

Charging refrigerant

6.7.1

About charging refrigerant

The outdoor unit is factory charged with refrigerant, but depending
on the field piping you have to charge additional refrigerant.
Before charging refrigerant
Make sure the outdoor unit's external refrigerant piping is checked
(leak test, vacuum drying).
Typical workflow
Charging additional refrigerant typically consists of the following
stages:
1
Determining how much you have to charge additionally.
2
Charging additional refrigerant (pre-charging and/or charging).
3
Filling in the fluorinated greenhouse gases label, and fixing it to
the inside of the outdoor unit.
6.7.2

Precautions when charging refrigerant

INFORMATION
Also read the precautions and requirements in the
following chapters:
▪ General safety precautions
▪ Preparation
WARNING
▪ Only use R410A as refrigerant. Other substances may
cause explosions and accidents.
▪ R410A contains fluorinated greenhouse gases. Its
global warming potential (GWP) value is 2087.5. Do
NOT vent these gases into the atmosphere.
▪ When charging refrigerant, always use protective
gloves and safety glasses.
NOTICE
If the power of some units is turned off, the charging
procedure cannot be finished properly.
NOTICE
Be sure to turn on the power 6 hours before operation in
order to have power running to the crankcase heater and
to protect the compressor.
NOTICE
Before starting charging procedures, check if the 7‑LEDs
display is as normal (see
page 
25). If a malfunction code is present, see
"11.3  Solving problems based on error codes"  on
page 30.
NOTICE
Close the front panel before any refrigerant charge
operation is executed. Without the front panel attached the
unit cannot judge correctly whether it is operating properly
or not.
NOTICE
In case of maintenance and the system (outdoor unit+field
piping+indoor units) does not contain any refrigerant any
more (e.g., after refrigerant reclaim operation), the unit has
to be charged with its original amount of refrigerant (refer
to the nameplate on the unit) and the determined additional
refrigerant amount.
6 Installation
"7.2.4 To access mode 1 or 2" on
Installer and user reference guide
19

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lrmeq4ay1

Table of Contents