13 Technical data
13.7

Technical specifications: Outdoor unit

Technical specifications
Specification
Casing material
Dimensions h×w×d
Weight
Operation range
▪ Evaporating temperature
▪ Outdoor temperature
(a)
Capacity
▪ Refrigerating capacity (medium temperature)
▪ COP
▪ Power input
PED
▪ Category
▪ Most critical part
▪ PS×V
Maximum number of indoor units connected
Heat exchanger
▪ Type
▪ Treatment
Fan
▪ Type
▪ Quantity
(b)
▪ Air flow rate
▪ Motor
▪ Model
▪ Output/pcs
Compressor
▪ Quantity
▪ Model
▪ Type
(c)
Sound level (nominal)
(d)
▪ Sound power
(e)
▪ Sound pressure
Refrigerant
▪ Type
▪ Charge
Refrigerant oil
Safety devices
(a)
Nominal capacities are based on evaporating temperature –10°C, outdoor temperature 32°C DB, and suction superheat 10°C.
(b)
Nominal at 230 V.
(c)
Sound values are measured in a semi-anechoic room.
(d)
Sound power level is an absolute value that a sound generates.
(e)
Sound pressure level is a relative value depending on the distance and acoustic environment. For more details, refer to sound level drawings in
the technical data book.
Installer and user reference guide
40
LRMEQ3
Painted galvanised steel
1345×900×320 mm
104 kg
–10~2°C
–10~43°C DB
5.90 kW
1
Compressor
167 bar×l
4
Cross fin
Anti corrosion
Propeller
2
106 m³/min
2
Direct drive
70 W
1
Inverter
Hermetically sealed scroll compressor
67 dBA
51 dBA
R410A
4.0 kg
FVC68D
High pressure switch
Fan driver overload protector
Inverter overload protector
PCB fuse
Air-cooled refrigeration condensing unit
LRMEQ4
8.40 kW
LRMEQ3+4AY1
4P442131-1 – 2016.03