Electrical specifications
Specification
Power supply
▪ Name
▪ Phase
▪ Frequency
▪ Voltage
Current
▪ Nominal running current (RLA)
(b)
▪ Starting current (MSC)
▪ Minimum circuit amps (MCA)
(d)
▪ Maximum fuse amps (MFA)
(e)
▪ Full load amps (FLA)
Voltage range
Wiring connections
▪ For power supply
(a)
RLA is based on evaporating temperature –10°C, outdoor temperature 32°C DB, and suction superheat 10°C.
(b)
MSC=the maximum current during startup of the compressor. ZEAS uses only inverter compressors. MCA must be used to select the correct field
wiring size. The MCA can be regarded as the maximum running current.
(c)
MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
(d)
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
(e)
FLA=nominal running current fan. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not
below or above listed range limits. Maximum allowable voltage range variation between phases is 2%.

For the user

14
About the system
NOTICE
For future modifications or expansions of your system:
A full overview of allowable combinations (for future
system extensions) is available in technical engineering
data and should be consulted. Contact your installer to
receive more information and professional advice.
14.1

System layout

a
b
c
a
Outdoor unit (ZEAS condensing unit)
b
Refrigerant piping
c
Indoor unit (Blower coil)
d
Indoor unit (Showcase)
15

Before operation

WARNING
This unit contains electrical and hot parts.
WARNING
Before operating the unit, be sure the installation has been
carried out correctly by an installer.
LRMEQ3+4AY1
Air-cooled refrigeration condensing unit
4P442131-1 – 2016.03
(a)
(c)
d
LRMEQ3
Y1
3N~
50 Hz
380-415 V
≤MCA
13.5 A
16 A
0.3+0.3 A
380-415 V +/– 10%
5G
CAUTION
It is not good for your health to expose your body to the air
flow for a long time.
CAUTION
To avoid oxygen deficiency, ventilate the room sufficiently
if equipment with burner is used together with the system.
CAUTION
Do not operate the system when using a room fumigation-
type insecticide. This could cause the chemicals to
become deposited in the unit, which could endanger the
health of those who are hypersensitive to chemicals.
16

Operation

16.1

Operation range

Use the system in the following temperature ranges for safe and
effective operation.
Outdoor temperature
Evaporating temperature
16.2

Operating the system

16.2.1

About operating the system

▪ To protect the unit, turn on the main power switch 6 hours before
operation.

14 About the system

LRMEQ4
≤MCA
Cooling
–10~43°C DB
–10~2°C
Installer and user reference guide
41