Guidelines When Installing A Sight Glass - Daikin LRMEQ3AY1 Installer And User Reference Manual

Air-cooled refrigeration condensing unit
Table of Contents

Advertisement

6 Installation
a
b
e
d
c
a
Service port
b
Stop valve cover
c
Hexagon hole
d
Shaft
e
Seal
To open the stop valve
1 Remove the stop valve cover.
2 Insert a hexagon wrench into the stop valve and turn the stop
valve counterclockwise.
3 When the stop valve cannot be turned any further, stop turning.
Result: The valve is now open.
2
3
1
4
To close the stop valve
1 Remove the stop valve cover.
2 Insert a hexagon wrench into the stop valve and turn the stop
valve clockwise.
3 When the stop valve cannot be turned any further, stop turning.
Result: The valve is now closed.
Closing direction:
To handle the stop valve cover
▪ The stop valve cover is sealed where indicated by the arrow. Take
care not to damage it.
▪ After handling the stop valve, make sure to tighten the stop valve
cover securely. For the tightening torque, refer to the table below.
▪ Check for refrigerant leaks after tightening the stop valve cover.
Installer and user reference guide
16
NOTICE
Thread-locking fluid. Before reattaching the stop valve
cover, apply thread-locking fluid to the screw thread (NOT
to the cover or sealing part). Otherwise, condensation
water might enter and freeze. Possible consequence:
Deformation,
refrigerant
malfunction.
a
b
b
c
a
Cover (do NOT apply thread-locking fluid)
b
Sealing part (do NOT apply thread-locking fluid)
c
Screw thread with thread-locking fluid
To handle the service port
▪ Always use a charge hose equipped with a valve depressor pin,
since the service port is a Schrader type valve.
▪ After handling the service port, make sure to tighten the service
port cover securely. For the tightening torque, refer to the table
below.
▪ Check for refrigerant leaks after tightening the service port cover.
NOTICE
Thread-locking fluid. Before reattaching the service port
cover, apply thread-locking fluid to the screw thread (NOT
to the cover or sealing part) . Otherwise, condensation
water might enter and freeze. Possible consequence:
Deformation,
refrigerant
malfunction.
a
b
c
a
Cover (do NOT apply thread-locking fluid)
b
Sealing part (do NOT apply thread-locking fluid)
c
Screw thread with thread-locking fluid
Tightening torques
Stop valve
Tightening torque N•m (turn clockwise to close)
size (mm)
Valve body Hexagonal
wrench
Ø9.5
5.4~6.6
4 mm
Ø15.9
13.5~16.5
6 mm
6.4.8

Guidelines when installing a sight glass

Install a sight glass on the liquid piping:
Diameter
9.5 mm
Where/how
Install the sight glass before the dryer, as near
to the outdoor unit as possible. Install
horizontally.
a Sight glass
b Dryer
leakage
and
compressor
leakage
and
compressor
Shaft
Cap (valve
Service
lid)
port
13.5~16.5
11.5~13.9
22.5~27.5
a
b
LRMEQ3+4AY1
Air-cooled refrigeration condensing unit
4P442131-1 – 2016.03

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lrmeq4ay1

Table of Contents