Inputs And Outputs Of The Vibration Module; Connecting The Analogue Inputs Of The Vibration Module - Schaeffler ProLink CMS User Manual

Hide thumbs Also See for ProLink CMS:
Table of Contents

Advertisement

5.4 Inputs and outputs of the vibration module

You can use 4 analogue inputs (Analog Input), 2 digital inputs (Digital Input) and 4 digital switching outputs (Digital
Out) on each vibration module of the ProLink device. The galvanic isolation of the vibration module is implemented
as follows:
Power supply 24 VDC: Electrically isolated
·
Communication (Ethernet): Electrically isolated
·
Inputs and outputs: Electrically isolated from supply and communication
·
Analogue and digital inputs: Common earth
·
Switching outputs: Common earth
·
The following sections provide some information about input and output connections and their configuration in the
Schaeffler SmartWeb software.
An illustration of all the connection options for the ProLink device can be found in the Connection overview
section.
Information on configuration options can be found in the section Further information
user documentation Schaeffler SmartWeb.
Here, you can:
Connect the analogue inputs of the vibration module
·
Connect the digital inputs of the vibration module
·
Connect the digital switching outputs of the vibration module
·

5.4.1 Connecting the analogue inputs of the vibration module

You can connect up to 4 analogue sensors, such as vibration sensors, to the analogue inputs of the vibration
module. The following wiring diagram shows the connection of an IEPE acceleration sensor: