Hydraulic Systems - Riello Gulliver BLU BGK0.1 Installation, Use And Maintenance Instructions

Light oil burners, one stage operation
Table of Contents

Advertisement

Available languages

Available languages

3.3

HYDRAULIC SYSTEMS

WARNING:
The pump is designed to allow working with two pipes. In
order to obtain one pipe working it is necessary to
unscrew the return plug (2), remove the by-pass screw
(3) and then screw again the plug (2), (see fig. 7).
It is necessary to install a filter on the fuel supply line.
Before starting the burner make sure that the return
pipe-line is not clogged. An excessive back pressure
would cause the damage of the pump seal.
SYSTEM NOT PERMITTED
IN GERMANY
D6328
PRIMING PUMP:
On the system in fig. 8 it is sufficient to loosen the suction gaugeconnection
(6, fig. 7) and wait until oil flows out.
On the systems in fig. 9 and 10 start the burner and wait for the priming.
Should lock-out occur prior to the arrival of the fuel, await at least 20 seconds
before repeating the operation.
The pump suction should not exceed a maximum of 0.4 bar (30 cm Hg).
Beyond this limit gas is released from the oil. Oil pipes must be completely tight.
In the vacuum systems (fig. 10) the return line should terminate within the oil
tank at the same level as the suction line. In this case a non-return valve is not
required. Should however the return line arrive over the fuel level, a non-re-
turn valve is required.
This solution however is less safe than previous one, due to the possibility of
leakage of the valve.
ONLY FOR ITALY
:
Automatic shut-off device as per Ministry of Internal Affairs' regulation no. 73 dated 7/29/71.
H = difference of level;
Fig. 8
meters
Fig. 9
L = max. length of the suction line;
8
1
2
3
L meters
H
I. D.
I. D.
8 mm
10 mm
0.5
10
20
1
20
40
1.5
40
80
2
60
100
4
GB
Fig. 7
D5487
4
5
6
1 - Suction line
2 - Return line
3 - By-pass screw
4 - Gauge connection
5 - Pressure adjuster
6 - Suction gauge connection
7 - Valve
8 - Auxiliary pressure test point
L meters
H
I. D.
meters
8 mm
0
35
0.5
30
1
25
1.5
20
2
15
3
8
3.5
6
Fig. 10
I. D. = internal diameter.
7
I. D.
10 mm
100
100
100
90
70
30
20
D6329
2694

Advertisement

Table of Contents
loading

This manual is also suitable for:

357 t137375003737511

Table of Contents