R410A DC Inverter VRF V4 Plus Individual Series 50Hz
More than two rows
When the outdoor unit is lower than the surrounding obstacle, refer to the layout used when the outdoor unit
is higher than the surrounding obstacle. However, to avoid cross connection of the outdoor hot air from
affecting the heat exchange effect, please add an air director onto the exhaust hood of the outdoor unit to
facilitate heat dissipation. See the figure below. The height of the air director is HD(namely H-h).Please
make the air director on site.
16
MCAC-VTSM-2014-04
Specifications & Performances
Need help?
Do you have a question about the VRF V4 Plus I Series and is the answer not in the manual?
Questions and answers
What the function of alphabet given in enc3 like abcdefg
In the Midea Series, ENC3 is used for setting the number of indoor units. The alphabet values in ENC3 correspond to numeric values as follows:
- 0–3: for indoor units 0–15
- 9–C: for indoor units 16–31