Response Timeout
Set up the timeout timer from 50ms to 100000ms.
If the set value is out of range, it will be
automatically changed to its maximum or minimum
value. The default is 300ms.
Scan Interval
Set up the time for scan interval, ranging from
20ms to 60000ms; the default is 3000ms.
Read/Write
Set up the access permissions for the mapped
register address;
Slave ID
Set up the corresponding slave communication
port. The value is between 1 and 247.
Add Mappings
Controller
Device types:
Address Type
Depending on the selected controller type change:
Slave Starting Address
Set up the slave starting address for read/write the
registers in a PLC.
Description
Read-only: The device regular read data from
appointed registers in the slave, but will not
update the data to the slave
Write-only: The device update the data to the
slave when the registers values was
changed, but will not read the data from the
slave
Read/write: The device regular read data
from appointed registers in the slave, will
update the data to the slave when the
registers values is changed.
Delta PLC: Delta DVP / AH / AS series PLCs
use this option.
Other: Use this option for non-Delta DVP / AH
/ AS series PLCs.
Delta PLC: The address type is "D"
Other: The address type is "W"
Delta PLC: Enter the internal D register
number. If you need to read / write D0,
please enter 0 here.
Cha p ter 3 In tr od ucti on to F unc tio ns
Default
300
30000
Read/Write
N/A
Delta DVP PLC
D
N/A
_3
3 - 3 1