Cisco ONS 15454 M6 Installation Manual page 69

Hide thumbs Also See for ONS 15454 M6:
Table of Contents

Advertisement

Installing the ONS 15454 M6 Shelf
Stop. You have completed this procedure.
NTP-G329 Remove the Deep-Front Panel of the ONS 15454 M6
Shelf
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
Caution
The deep-front panel does not have a hinge and cannot be rotated like a standard door. Rotating the deep-front
panel can damage the deep-front panel, shelf hinges, other devices and cables placed below the ONS 15454
M6 shelf.
Note
When the deep front-panel is installed, the total chassis depth is 12.9 inches. The deep front-panel extends
from the rack by 1.8 inches.
Procedure
Step 1
Remove the end of the ground strap cable that is connected to the exterior of the deep-front panel (see the
following figure).
NTP-G329 Remove the Deep-Front Panel of the ONS 15454 M6 Shelf
This procedure removes the deep-front panel of the ONS 15454 M6 system.
• #2 Phillips Dynamometric screwdriver
• Socket (6/32 standard) and socket wrench to tighten or loosen the ground
nut
NTP-G252 Install the ONS 15454 M6 Shelf , on page 24
NTP-G327 Install the Deep-Front Panel of the ONS 15454 M6 Shelf, on
page 62
• Connect the chassis to the office ground. For detailed instructions on how
to ground the chassis, see the
for Cisco CPT and Cisco ONS
Required
Onsite
None
Electrostatic Discharge and Grounding Guide
Platforms.
Installing the ONS 15454 M6 Shelf
69