Installing the ONS 15454 M6 Shelf
Cable
AC power cable - ARG left exit
AC power cable - ARG right exit
AC power cable - AUS left exit
AC power cable - AUS right exit
AC power cable - UK left exit
AC power cable - UK right exit
AC power cable - KOR left exit
AC power cable - KOR right exit
AC power cable ANSI 110VAC left exit
AC power cable ANSI 110VAC right exit
AC power cable ANSI 220VAC left exit
AC power cable ANSI 220VAC right exit
AC power cable for data center left exit
AC power cable for data center right exit
DLP-G572 Connect Office Power (DC) to the ONS 15454 M6 Shelf (ANSI Only)
Purpose
Tools/Equipment
DLP-G572 Connect Office Power (DC) to the ONS 15454 M6 Shelf (ANSI Only)
PID
15454-M-CBL-LARG=
15454-M-CBL-RARG=
15454-M-CBL-LAUS=
15454-M-CBL-RAUS=
15454-M-CBL-L-UK=
15454-M-CBL-R-UK=
15454-M-CBL-LKOR=
15454-M-CBL-RKOR=
15454-M-ACCBL-L=
15454-M-ACCBL-R=
15454-M-ACCBL-L2=
15454-M-ACCBL-R2=
15454-M-ACL6-L=
15454-M-ACL6-R=
This task connects DC power to the ONS 15454 M6 (ANSI Only).
• #2 Phillips Dynamometric screwdriver
• Medium slot-head screwdriver
• Small slot-head screwdriver
• Wire wrapper
• Wire cutters
• Wire strippers
• Crimp tool
• Open-end wrench or hex tube screw driver
• Fuse panel
• Power cable (from fuse and alarm panel to assembly), #8 AWG, copper
conductors, 194 degrees F (90 degrees C)
• Ground cable #6 AWG stranded
• Listed pressure dual-holes lugs suitable for #8 AWG copper conductors
Installing the ONS 15454 M6 Shelf
107