Sanyo SAP-K71GJA Technical & Service Manual page 48

Split system air conditioner
Table of Contents

Advertisement

B. Circuit breaker trips in several minutes after turning the air conditioner on.
There is a possibility of short circuit.
Check capacity of circuit breaker.
Capacity of circuit breaker is
suitable.
Measure resistance of outdoor fan
motor winding.
Measure resistance of compressor
motor winding.
9-2-2. Neither indoor nor outdoor unit runs.
A. Power is not supplied.
• Check power supply.
Power is being supplied to the
outdoor unit.
B. Check remote control unit.
• Try to run with another remote
control unit.
OK
First remote control unit is defective.
• Check for residue buildup on
transmitter of remote control unit.
• Check for residue buildup on remote
control receiver on front of indoor
unit.
Replace with suitable
NO
one (larger capacity).
Circuit breaker
is tripped.
NO
Power failure
Does not run.
45
Reset breaker.
Wait for recovery
or contact power
company.
Refer to Step C below.
Clean transmitter.
Clean receiver.