Static Test Procedure; Test Equipment; Connection - Leroy-Somer Nidec R180 Installation And Maintenance Manual

Avr
Table of Contents

Advertisement

Electric Power Generation

8 - STATIC TEST PROCEDURE

8.1 - Test equipment

- 3-phase variac
- AC/DC voltmeter
- 100 Watt bulb
- 1 K potentiometer
- 250V/110V transformer
Installation and maintenance
R180
AVR

8.2 - Connection

- Connect the 100 W bulb between the F1
and F2 terminals on the AVR
- Connect the 110V transformer output to
X1 and X2 on the AVR
- Connect the 250V end of the transformer
to U and N on the variac
- V output on the variac to V terminal on
the AVR
- W on the variac to W terminal on the AVR
- Connect the 1 KΩ potentiometer to A1
and A2
Bulb
5599 en -
2020.07 / f
13