Speed controller for asynchronous motors (110 pages)
Summary of Contents for Leroy-Somer R220 VSG+CCM
Page 1
4705 en - 2013.05 / b Rotor Stator Armature U1 U2 U3 V1 V2 V3 W1 W2 W3 Exciter VOLT (-) (+) R 220 VSG Diode bridge R220 VSG + CCM LEM batt. LEM load 300 A A.V.R. multi batteries dedicated fuse Installation and maintenance PT100...
Page 2
LEROY-SOMER Installation and maintenance 4705 en - 2013.05 / b R220 VSG + CCM A.V.R. This manual concerns the alternator A.V.R. which you have just purchased. We wish to draw your attention to the contents of this maintenance manual. By following certain important points during installation, use and servicing of your A.V.R., you can...
IP20 minimum total protection (it must only be installed on LS alternators in the appropriate location so that when viewed externally, it has a higher degree of protection than IP20). Copyright 2005 : MOTEURS LEROY-SOMER This document is the property of : MOTEURS LEROY-SOMER It may not be reproduced in any form without prior authorization.
LEROY-SOMER Installation and maintenance 4705 en - 2013.05 / b R220 VSG + CCM A.V.R. 2.2 - CCM characteristics The CCM general view is given by the following figure: Battery Battery Generator Speed type capacity maximum change selection setting current setting Θ...
Page 6
LEROY-SOMER Installation and maintenance 4705 en - 2013.05 / b R220 VSG + CCM A.V.R. 2.2.2 - CCM terminals description 2.2.3 - How does the CCM work A. Regulator link (Reg Out) The following convention will be used is this...
Page 7
LEROY-SOMER Installation and maintenance 4705 en - 2013.05 / b R220 VSG + CCM A.V.R. 2.2.3.2 - Light-Emitting Diode (LED) the engine is started by the ON/OFF relay status A3. The relay must go to low speed when these two following conditions are achieved: A.Charging LED :...
LEROY-SOMER Installation and maintenance 4705 en - 2013.05 / b R220 VSG + CCM A.V.R. 3-INSTALLATION - Excitation circuit E+, E- must not be left open when the machine is running : AVR COMMISSIONING damage will occur. 3.1 - Electrical checks on the AVR 3.2.1.1 - R220 VSG field weakening...
LEROY-SOMER Installation and maintenance 4705 en - 2013.05 / b R220 VSG + CCM A.V.R. 3.3 - Electrical faults Fault Action Effect Check/Cause The alternator builds up and its voltage is still correct when the - Lack of residual magnetism battery is removed.
LEROY-SOMER Installation and maintenance 4705 en - 2013.05 / b R220 VSG + CCM A.V.R. 4 - SPARE PARTS 4.1 - Designation Description Type Code A.V.R. R 220 VSG AEM 110 RE 035 A.V.R. AEM 056 CT 001 4.2 - Technical support service Our technical support service will be happy to provide any information you require.
LEROY-SOMER Installation and maintenance 4705 en - 2013.05 / b R220 VSG + CCM A.V.R. 5 - ANNEX Types of batteries supported by the CCM 5.1 - Battery 1: OpZV type End of charge condition: the charge current is less than 3% of the total capacity of the...
LEROY-SOMER Installation and maintenance 4705 en - 2013.05 / b R220 VSG + CCM A.V.R. 5.2 - Battery 2: SBS EON type End of charge condition: the charge current is less than 3% of the total capacity of the battery...
LEROY-SOMER Installation and maintenance 4705 en - 2013.05 / b R220 VSG + CCM A.V.R. 5.3 - Battery 3: Saft Evolion type End of charge condition: the charge current is less than 3% of the total capacity of the battery...
LEROY-SOMER Installation and maintenance 4705 en - 2013.05 / b R220 VSG + CCM A.V.R. 5.4 - Battery 4: Exide A600 type End of charge condition: the charge current is less than 3% of the total capacity of the battery...