Technical Specification - Leroy-Somer Nidec R180 Installation And Maintenance Manual

Avr
Table of Contents

Advertisement

Electric Power Generation

3 - TECHNICAL SPECIFICATION

1
Sensing input
2
Voltage range high
3
Voltage range low
4
Droop
5
Droop range
6
PMG input power
7
AREP+ input power
8
Excitation current
9
Regulation
10
Maximum excitation limit
11
Maximum excitation limit
delay
12
Under frequency protection
13
Slope
14
Remote potentiometer
15
Accessory Input
16
Loss of sensing
17
Weight
18
Dimensions
19
Temperature range
20
Storage temperature range
21
Thermal drift
22
Fuse
6
Installation and maintenance
R180
AVR
3-ph/2-ph - 220/230/240/380/400/415 volts for
50 Hz
3-ph/2-ph - 208/240/277/380/416/440/480 volts for
60 Hz
300V to 530V
180V to 310V
1 and 5A AC in U phase
8% droop at 0.8 PF
Continuous: 240V RMS +10%
Momentary 5 s: 240V RMS + 30
Up to 240 Hz
Continuous: 250V peak+10%
Momentary 10 s: 350V peak +5% - Up to 75 Hz
6A DC continuous
9A for 5 seconds (short-circuit operation)
± 0.5% at AVR sensing terminals
6A DC (factory setting)
30 sec. (factory setting)
48.5 Hz/58.5 Hz for 50 Hz/60 Hz operation
1.2X (120%) V/Hz
1 kOhm for ± 10% adjustment
± 4.5V DC for ±15%
Shuts down after 5 sec. when sensing open
500 g approximate
140 mm x 115 mm x 70 mm
-25ºC to +70ºC
-40ºC to +80ºC
0.5% for 20ºC change
FST 10A 250V
5599 en -
2020.07 / f

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents