GE Hydran 201i Installation Manual page 34

Hide thumbs Also See for Hydran 201i:
Table of Contents

Advertisement

Hydran* 201i Installation Guide
3. Wait a few minutes and touch the back of the heating plate. It should be
warm if the LED
heated.
4. After the H201Ti has performed the first-time power-up sequence and then
the self-test sequence, verify it displays the following messages at the rate of
one every five seconds:
• Alarm messages (if any)
• Gas level
• Gas hourly trend
• Gas daily trend
• Date and time
5. If the H201Ti is linked to a Hydran 201Ci- C Controller, power them up and
verify the H201Ci-C's operation by observing the following LEDs:
• The Supervisory Link Supply indicator (green, DS12) is lit.
• The Heater indicator (yellow, DS8):
o
o
o
6. If the H201Ti is linked to a Hydran 201Ci-1 Controller, power them up and
verify the H201Ci-1's operation by observing the following LED's and
indicators:
• The Supervisory Link Supply indicator (green, DS12) is lit.
• The Heater indicator (yellow, DS8):
o
o
o
• The two alarm indicators of the door-mounted push-buttons are off.
• The Alarm 1 (Gas High) indicator (yellow, DS10) is off.
• The Alarm 2 (Gas High-High) indicator (yellow, DS9) is off.
• The System OK indicator (yellow, DS11) is lit.
Note: The H201Ci-1's display must also be functional.
7. The H201Ti requires set-up (alarms, temperature, data logging) and
commissioning for normal use. Please refer to the Hydran 201i System
Instruction Manual.
17996 Rev5, August 2013
C is blinking. This indicates that the sensor is being
It must initially be lit if the ambient temperature is below
approximately 25 °C (77 °F).
After a while, it must flash as the enclosure temperature reaches the
above set point.
It must remain off if the ambient temperature exceeds the set point.
It must initially be lit if the ambient temperature is below
approximately 25 °C (77 °F).
After a while, it must flash as the enclosure temperature reaches the
above set point.
It must remain off if the ambient temperature exceeds the set point.
Page 35

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents