5.7 Fastening the Hydran 201Ti to the Brass Adaptor

1. Using the supplied 3/16-in Allen key, fasten the H201Ti's heating plate to the
brass adaptor with the six 1/4-28 cap screws. See Figure 17 below.
CAUTION
Note: When the H201Ti is installed horizontally, the terminals must be facing up
and located under the sensor.
sampling port remain easy to access.
2. Plug the twist-lock female connector of the sensor cable to the male
connector behind the Hydran 201 sensor,
Page 30
Figure 17: Fastening the Heating Plate to the Brass Adapter
Be careful not to squeeze the nearby electrical wires between
the lock washers and the heating plate or not to damage the
supervisory link (and analog output) termination board.
Also, ensure that both the bleed screw and
Hydran* 201i Installation Guide