10.2. Installation instruction
In installation, please check specially the below items:
• If the connected units quantity and the total capacity is in the allowable range?
• If the refrigerant pipe length is in the limited range?
• If the pipe size is proper? And if the pipe is installed horizontally?
• If the branch pipe is installed horinzontally or vertically?
• If the additional refrigerant is counted correctly and weighed by the standard balance?
• If there is refrigerant leakage?
• If all the indoor power supplies can be on/off simultaneously?
• If the power voltage is in compliance with the data marked on the rating label?
• If the address of indoors and outdoors has been set?
Before installation
1) Before installation, check if the model, power supply, pipe, wires and parts purchased respectively are correct.
2) Check if the indoors and outdoors can be combined as the following.
HP
Capacity (100W)
8
224
10
280
12
335
14
400
16
450
18
504
20
560
22
615
24
680
26
735
28
800
30
850
32
900
34
954
36
1008
38
1064
40
1120
42
1175
44
1230
46
1300
48
1350
50
1404
52
1458
54
1512
56
1568
58
1624
60
1680
62
1735
64
1790
66
1845
Outdoor
Combination type
Single (8HP)
Single (10HP)
Single (12HP)
Single (14HP)
Single (16HP)
Single (18HP)
Single (20HP)
Single (22HP)
Combination (335+335)
Combination (335+400)
Combination (400+400)
Combination (400+450)
Combination (450+450)
Combination (450+504)
Combination (504+504)
Combination (504+560)
Combination (560+560)
Combination (560+615)
Combination (615+615)
Combination (400+450+450)
Combination (450+450+450)
Combination (450+450+504)
Combination (450+504+504)
Combination (504+504+504)
Combination (504+504+560)
Combination (504+560+560)
Combination (560+560+560)
Combination (560+560+615)
Combination (560+615+615)
Combination (615+615+615)
Indoor
Indoor Qty
Total indoor capacity (HP)
1~15
1~17
1~20
1~24
1~27
1~30
1~33
1~36
1~40
1~43
1~46
1~50
1~53
1~57
1~60
1~64
1~64
1~64
1~64
1~64
1~64
1~64
1~64
1~64
1~64
1~64
1~64
1~64
1~64
1~64
65
Gather
pipe
4~10.4
-
5~13
-
6~15.6
-
7~18.2
-
8~20.8
-
9~23.4
-
10~26
-
11~28.6
-
12~31.2
13~33.8
14~36.4
15~39
16~41.6
17~44.2
HZG-R20B
18~46.8
19~49.4
20~52
21~54.6
22~57.2
23~59.8
24~62.4
25~65
26~67.6
27~70.2
28~72.8
HZG-R30B
29~75.4
30~78
31~80.6
32~83.2