Haier MRV 5-RC VP1-112B Service Manual page 179

Table of Contents

Advertisement

Failure code
Indoor unit LED status
Outdoor
digital
display tube:
22-2
Indoor wired
Outdoor unit LED status
controller:
16
1. Model
MRV 5-RC series
2. Abnormity detection method
◆ Check if the sensor
connection is normal;
◆ Check if resistance
characteristic of the sensor is
normal;
◆ Check if the temperature
loop acquired by the PCB is
normal.
3. Abnormity confirmation
conditions
It is detected that the AD value
is below 11 (open circuit) or
above 1012 (short circuit)
for 60 seconds continuously,
and no alarm is given during
defrosting and within 3 minutes
at the end of defrosting.
4. Possible causes
◆ The connection of sensor is
not secure;
◆ The sensor is broken;
◆ The sensor is with
resistance drift;
◆ The temperature acquired
by PCB is not accurate.
Normal
Failure diagnosis and troubleshooting
Diagnosis
Check if the corresponding
connector of sensor is normal
Check if resistance
characteristic of the sensor
is normal
Check if the temperature
l o o p a c q u i r e d b y t h e
computer board is normal
LED5
Failure description:
Suction temperature sensor:
20 times
Ts failure
LED1
LED2
Normal
N
Y
N
Y
Y
176
Troubleshooting
Replace it correctly by after-
sales personnel on site.
Replace it correctly by after-
sales personnel on site.
Replace it correctly by after-
sales personnel on site.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mrv 5-rc vp1-180bMrv 5-rc vp1-280bMrv 5-rc vp4-450bMrv 5-rc av08imvuraMrv 5-rc av10imvuraMrv 5-rc av12imvura ... Show all

Table of Contents