Failure code
Outdoor
Indoor unit LED status
digital
display tube:
43-0, 1
Indoor wired
Outdoor unit LED status
controller:
2B
1. Model
MRV 5-RC series
2. Abnormity detection method
◆ Check if the temperature
detected by the oil temperature
sensor is correct.
◆ Check the outdoor unit
SV31, SV32, LEVb, etc. for
abnormal leakage and check
if the detected temperature is
correct;
◆ Check if the shutdown
indoor unit LEV of unit is closed
tightly, and if the running indoor
unit fan operates normally.
3. Abnormity confirmation
conditions
Td1/Td2-CT≤10°C lasts for
5min.
4. Possible causes
◆ The probe of oil temperature
sensor falls off or is with
unsecure connection;
◆ The probe of oil temperature
sensor is misplaced;
◆ The oil temperature sensor
is with resistance drift;
◆ The outdoor unit LEVb,
SV31 and SV32 are with
leakage;
◆ The terminal of outdoor
unit LEVa1, 2 and LEVb is
connected incorrectly;
◆ For the unit, there is LEV
leakage in shutdown indoor
unit and non-operation of fan in
operating indoor unit;
◆ The system is filled with
excessive refrigerant.
◆ The operation environment
is beyond the allowed range.
Normal
Diagnosis and troubleshooting
Diagnosis
Check if the resistance of discharging
temperature sensor is correct.
Check if the sensor probe is secure
and if the position is correct.
Check if the indoor unit LEV of "OFF"
is closed tightly and if the indoor unit
fan of "ON" is normal.
Check if the terminal of outdoor unit
terminal LEVb, SV31 and SV32 is
connected properly or is closed tightly.
Check if the outdoor unit LEVa1,
2 and LEVb are connected
properly and correctly.
Check if the unit is filled with
excessive refrigerant.
Fill with refrigerant in
accordance with standard
quantity.
LED5
Failure description:
Outdoor unit compressor discharging tem-
20 times
perature (Td1, Td2) too low failure
LED1
LED2
Normal
N
Y
N
Y
N
Y
N
Y
N
Y
N
Y
193
Troubleshooting
Replace the discharging
temperature sensor by after-
sales personnel on site.
Replace it correctly by after-sales
personnel on site.
[Note]: Check if it is inserted,
connected and intersected with
another compressor, especially
when a single compressor operates.
R e p l a c e t h e p o o r v a l v e ( w i t h
leakage) and fan correctly by after-
sales personnel on site.
R e p l a c e t h e p o o r v a l v e ( w i t h
leakage) and fan correctly by after-
sales personnel on site.
Replace it correctly by after-sales
personnel on site.
C h e c k i f t h e c o m p u t e r b o a r d
can normally control the related
electronic expansion valve and
solenoid valve, if not, replace it.