Operation (Normal Conditions)

TURNING THE UPS OFF

• Press the front "OFF" button. Your load will still be energized. The inverter is now off, but your UPS is not fully deactivated. The LCD Display
will show "ON BYPASS."
• Turn the Main Input Switch and Bypass Input Switch Circuit Breakers OFF. Your load will no longer be energized, and the LCD display will be dark.
NOTE: If the UPS System remains off for an extended period of time, it should be turned back on periodically to allow the internal batteries to
recharge. The UPS System should be turned on and the internal batteries should be recharged at least one uninterrupted 24-hour period every
3 months. Failure to provide periodic recharge time may cause irreversible battery damage.

SELF-TESTING

When you turn the UPS ON, it will perform a brief self-test. See charts below for display sequences.
Display sequence when AC input power is present:
SELF TESTING...
RECTIFIER OK
CHARGER OK
BATTERY OK
DC TO DC OK
INVERTER TEST

LCD DISPLAY SELECT BUTTON

Momentarily press the "SELECT" button on the front panel to browse through different power readings on the LCD Display.
BYPASS
OUTPUT
R: XXXV R: XXX.XV
(Bypass & Output Voltage)
S: XXXV
S: XXX.XV
T: XXXV
T: XXX.XV
Press "SELECT" Button
OUTPUT
LOAD
R: XXX%
XXX.XA
(Output Load & Current)
S: XXX%
XXX.XA
T: XXX%
XXX.XA
Press "SELECT" Button
MAINS
INVERTER
R: XXXV
R: XXX.XV
(Mains & Inverter Voltage)
S: XXXV
S: XXX.XV
T: XXXV
T: XXX.XV
Press "SELECT" Button
BYPASS:
XX.X Hz
MAINS:
XX.X Hz
(Bypass, Mains, Output & Inverter Frequency)
OUTPUT:
XX.X Hz
INVERTER: XX.X Hz
Press "SELECT" Button
CHARGE
FLOATING
CHARGER: XXX.XV
(Charger Mode, Charger/Battery Voltage & Battery Percentage)
BATTERY: XXX.XV
BATTERY: XXX.X%
Press "SELECT" Button
SN:
XXX
DC BUS:
XXV - XXV
(Serial Number, DC BUS Voltage, Temperature & Firmware Version)
TEMP:
XXX.X˚C
VERSION:
XXX
Press "SELECT" Button
ON:
UPS START
OFF:
UPS BYPASS
(Button Functions)
SEL:
UPS MESSAGE
ENT:
SET UPS
Press "SELECT" Button
(continued)
Display sequence when AC input power is absent:
(possible only with the "Battery Start" Switch)
SELF TESTING...
BATTERY OK
DC TO DC OK
INVERTER TEST
8