Operation (Special Conditions); Operation On Bypass-Voltage Out Of Range; Inverter On Warnings; Operation Under Shutdown - Tripp Lite SmartOnline 3-Phase 30kVA Owner's Manual

3-phase 20kva & 30kva intelligent true on-line ups systems
Hide thumbs Also See for SmartOnline 3-Phase 30kVA:
Table of Contents

Advertisement

Available languages

Available languages

Operation (Special Conditions)

OPERATION ON BYPASS—VOLTAGE OUT OF RANGE
While in Bypass Mode, the UPS monitors the input voltage, which on Bypass equals the output voltage. If the output voltage passes out of an acceptable
range (between 15% higher and 20% lower than nominal), the UPS displays the condition on its LCD and stops supplying output power to its load. If
power levels return to an acceptable level, the UPS resumes supplying power to the load, and its LCD reports that output voltage was too high or too
low at one time, but has returned to nominal.
Bypass Voltage Condition
>15% Higher than Nominal
>20% Lower than Nominal
Was Too High, Now Nominal
Was Too Low, Now Nominal

INVERTER ON WARNINGS

When the inverter is ON, the LCD Display may show any one of the following warnings:
Condition
UPS Output Overload
UPS Charger Failure
Abnormal Input Frequency
Abnormal Input Phase
Battery is Depleting*
Battery Charge is Nearly Depleted*
* During a prolonged blackout, users should save files and shut down connected equipment.
The "BATTERY LOW" message indicates the UPS's batteries are nearly out of power and UPS shut down is imminent.

OPERATION UNDER SHUTDOWN

Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: For all conditions, the "Input,"
"Output" and "Bypass" LEDs will be illuminated.
Condition
Overload Shutdown
UPS Output Short Circuit
Overtemperature
DC BUS Overvoltage
DC BUS Failure
LCD Display Message
BYPASS HI NO O/P
BYPASS LO NO O/P
BYPASS WAS HI
BYPASS WAS LO
LCD Display Message
OVERLOAD 110%
CHARGER FAILURE
FREQUENCY ERROR
PHASE ABNORMAL!
ON BATTERY
BATTERY LOW
LCD Display Message
ON BYPASS
OVERLOAD 150%
SHUTDOWN...
VERSION: XXXXXXX
ON BYPASS
SHORT CIRCUIT!
SHUTDOWN...
VERSION: XXXXXXX
ON BYPASS
HIGH TEMP!
SHUTDOWN...
VERSION: XXXXXXX
ON BYPASS
DC BUS O.V.P.!
SHUTDOWN...
VERSION: XXXXXXX
ON BYPASS
DC BUS FAIL!
SHUTDOWN...
VERSION: XXXXXXX
Condition
R/S/T Inverter Output Failure
Low Battery
Remote Shutdown
Emergency Stop
9
LCD Display Message
ON BYPASS
R OUTPUT FAIL!
SHUTDOWN...
VERSION: XXXXXXX
BYPS OFF NO O/P
LOW BATTERY!
SHUTDOWN...
VERSION: XXXXXXX
BYPS OFF NO O/P
REMOTE SHUTDOWN
SHUTDOWN...
VERSION: XXXXXXX
BYPS OFF NO O/P
EMERGENCY STOP!
SHUTDOWN...
VERSION: XXXXXXX