Sw Mode Setting Via Jumper "J4; Address Setting - Panasonic External Presentation unit 1728 Technical Description

Hide thumbs Also See for External Presentation unit 1728:
Table of Contents

Advertisement

Panasonic Electric Works Fire & Security Technology Europe AB
MEW00290 Rev: 1
6.1.1
6.2
Technical Description External Presentation unit 1728
LANGUAGE SETTING!
Language: XXXXXXX
can be changed to one of the following languages:
XXXXXXX
- English
- Danish
- Swedish
Scroll to the wanted language with the push button "P1" (black).
Store the selected language with the push button "P2" (yellow) and the
unit will automatically be ready for the "Address setting ", see below.

SW mode setting via jumper "J4"

An ext. Presentation unit in operation
mode setting" via the jumper "J4" in the unit.
10
momentarily.
When the ext. Presentation unit is ready for the "SW mode setting"
this is indicated by the LED "Alarms queued" (L2). The back-light is
turned on and the following information is shown in the display:
MODE SETTING!
Type: XXXXXXXXXXXX
Continue in accordance with chapter "SW mode setting", page 11.

Address setting

After the SW mode setting or after the language setting (see above),
the ext. Presentation unit is ready for the "address setting".
As an alternative, one
ready for the "address setting" directly via the c.i.e. (menu H5/A9).
See the following chapter.
When the ext. Presentation unit is ready for the "address setting" this
is indicated by the LED "Alarms queued" (L2). The back-light is
turned on and the following information is shown in the display:
ADDRESS SETTING
Address: XX
XX can be changed to the following:
For an ext. Presentation unit with SW mode 1728 - 1587, the address
12
can be set to 00-15.
10
If "J4" is not removed, the ext. Presentation unit will not enter its normal
operation mode after the restart but start from the beginning again, ready for
the SW mode setting.
11
Or all the ext. Presentation units connected to the same Ext. FBP / DU
interface board 1587.
12
Normally should not more than eight units be connected to one Ext. FBP /
DU interface board 1587, if not ext. power supply is used.
Change = Black
Store = Yellow
7
will be ready for the "SW
Change = Black
Store = Yellow
11
ext. Presentation unit in operation can be
Change = Black
Store = Yellow
(Default is "00".)
12
Shunt "J4"