Restart - Panasonic External Presentation unit 1728 Technical Description

Hide thumbs Also See for External Presentation unit 1728:
Table of Contents

Advertisement

Panasonic Electric Works Fire & Security Technology Europe AB
MEW00290 Rev: 1
9
Technical Description External Presentation unit 1728

Restart

The ext. Presentation unit will restart:
• After the unit is powered up
• If the jumper "JP1" is shunted momentarily
• After address setting (i.e. after "P2" is pressed).
• If the contact with the Control unit is OK again after "
contact with Control unit
During the restart will in the display be shown (no back-light):
"Checking program memory..."
and after that (very quickly)
"Program memory OK."
and
"SSD memory OK."
All LED:s will be turned on during the restart.
If there is a program memory fault, there will be a fault message in the
display:
"Memory fault in program area (n)"
The ext. Presentation unit will not work.
There will also be a fault message in the c.i.e.:
In the EBL512 c.i.e.:
"FAULT:
Comm, EPU xx, 1587 board x, CU xx"
In the EBL128 c.i.e.:
"FAULT:
No reply EPU x
If there is an SSD (Site Specific Data) memory fault or no SSD
downloaded, there will be a fault message in the display:
"SSD memory fault"
The ext. Presentation unit will work since the user definable text
messages will be sent out from the c.i.e.
There will also be a fault message in the c.i.e.:
In the EBL512 c.i.e.:
"FAULT:
SSD, EPU xx, 1587 board x, CU xx"
In the EBL128 c.i.e.:
"FAULT:
Site specific data (SSD), EPU x
".
.
18
No
(n=1 or 2).
.
.
.