Technical Description External Presentation unit 1728
"FAULT:
SSD, EPU xx, 1587 board x, CU xx"
See chapter "Restart", page 18.

EBL128 c.i.e.

"FAULT:
No reply EPU x
The contact with the ext. Presentation unit is interrupted. Check
the cable and all connections. Is a correct / complete SSD
download (via Win128) performed? Check the address setting,
SW mode setting, etc. See also chapter "Restart", page 18.
"FAULT:
EPU x "
The ext. Presentation unit is programmed (via Win128) as
another type of unit or there is a fault in the ext. Presentation
unit.
"FAULT:
Site specific data (SSD), EPU x
See chapter "Restart", page 18.
.