Wiring Diagram; Power Wiring; Communication Wiring - Carrier 40VM900010 Installation And Operating Instructions Manual

Dls vrf interface, variable refrigerant flow system, indoor unit interface
Table of Contents

Advertisement

WIRING DIAGRAM

TRANSFORMER
RED
L1 L2
TERMINAL
POWER INPUT
NOTES:
1. The address set through ENC1 and SW7 must be consistent with the address of connect in indoor unit.
2. The set temperature unit through SW2_1 must be consistent with central controller, wired controller, and indoor units.

POWER WIRING

Phase
Power
Volt and
Frequency
Fuse on board
Wire
Fig. 4 —Power Input
RED
BLACK
CN8
YELLOW
YELLOW
CN6
CN1
CN54
Y/G
BLACK
Control port of
auxiliary heater etc.
( Voltage range: 0-24V AC/DC)
( Current range: 0-1A)
Fig. 3 —Wiring Diagram
1-Phase
230V-60Hz
5A/250VAC
2-core stranded shielded cable
18AWG
Y/G
CN7
LED1
CN5
DEBUG
ON
ON
1 2
ENC2 ENC1 SW7
CN3
CN4
X E Y
X E Y

COMMUNICATION WIRING

Type: 2-core stranded shielded cable
Diameter: AWG 18
Maximum wiring length:
• Within 3937 ft. between the ductless indoor unit and the
DLS VRF interface
• Within 3280 ft. between the touchscreen central
controller and the DLS VRF interface
• Within 820 ft. between the wire controller and DLS VRF
interface
Touch Screen
DLS VRF interface 1#
Controller
(TSCC)
CN3
X E Y
X E Y
X Y E
Ductless
Indoor
unit 1#
Fig. 5 —Communication Wiring
4
ON
ON
1 2
SW2
CN2
HB HA
DLS VRF interface M#
CN4
CN2
CN3
CN4
X E Y
HB HA
X E Y X E Y
Matched
resistance
X Y E
VRF
Ductless
controller
Indoor
controller
unit N#
Note:
CN2
HB HA
VRF