Inspection and maintenance
▶ Rinse the heat exchanger with water from the top.
Fig. 94 Rinsing the heat exchanger
▶ Clean the condensate tray (with reversed brush).
Fig. 95 Cleaning the condensate tray
▶ Rinse the heat exchanger with water from the top.
▶ Clean the condensate trap connection.
▶ Close the inspection opening again using a new gasket and tighten
the screws with a torque between 4.1 ft-lbs (5.5 Nm) and 5.1 ft-lbs
(7.0 Nm).
70

15.1.7 Cleaning condensate trap

▶ Remove condensate trap (steps 1 and 2) and check heat exchanger
orifice for clear passage.
6 720 612 664-18.1R
Fig. 96 Removing the condensate trap
▶ Remove and clean the condensate trap lid.
▶ Check condensate hose and clean if necessary.
▶ Fill the condensate trap with approx. 1 cup (1/4 l) of water and
reinstall it.

15.1.8 Checking the mixer diaphragm

▶ Open the mixer unit.
▶ Carefully remove the diaphragm from the fan air intake and check for
contamination and cracks.