Faults That Are Not Shown On The Display - Bosch Greenstar FS Series Installation And Maintenance Instructions For Contractors

Residential gas condensing boiler
Table of Contents

Advertisement

17.3

Faults that are not shown on the display

Appliance faults
Combustion noise too loud; rumbling noises
Flow noises
Heating-up takes too long
Flue gas readings incorrect; CO levels too high
Violent ignition, poor ignition
DHW has unpleasant odor or has a dark color
Set supply temperature (e.g. of the FW200 control)
exceeded
Condensate in air box
DHW temperature is not reached (combi boilerKWB..-3A
only)
Heatronic is flashing (i.e. all buttons, all display segments,
burner indicator etc. are flashing)
Table 41 Faults not shown on the display
Greenstar FS/Combi FS – 6 720 810 590 (2020/04)
Elimination
▶ Insert code plug correctly; replace if defective.
▶ Check gas type.
▶ Check inlet gas pressure; adjust if defective.
▶ Check flue gas system; clean or repair if defective.
▶ Check gas/air ratio in the combustion air and flue gas; replace gas valve if defective.
▶ Set pump speed correctly to match maximum output.
▶ Set pump mode.
▶ Set pump speed correctly to match maximum output.
▶ Set pump mode.
▶ Check gas type.
▶ Check inlet gas pressure; adjust if defective.
▶ Check flue gas system; clean or repair if defective.
▶ Check gas/air ratio in flue gas; replace gas valve if defective.
▶ Check gas type.
▶ Check inlet gas pressure; adjust if defective.
▶ Check power supply.
▶ Check electrodes for visual damage; replace if defective.
▶ Check flue gas system; clean or repair if defective.
▶ Check gas/air ratio; replace gas valve if defective.
▶ Check gas valve; replace if defective.
▶ Check burner; replace if required.
▶ Perform thermal disinfection of the DHW circuit.
▶ Replace sacrificial anode in the tank (if installed).
▶ Consult local water department.
▶ Switch off automatic anti-cycle timer, i.e., set value to 0.
▶ Set the required anti-cycle timer, e.g. default setting of 3 minutes.
▶ Insert diaphragm in the mixer unit per installation instructions; replace if defective.
▶ Insert code plug correctly; replace if defective.
▶ Check whether voltage (120 VAC) is present between terminal 1 and terminal 3; repair
if defective.
▶ Check turbine; replace if defective.
▶ Replace fuse Si 3 (24 V) (6.3 A fuse according to IEC default).
Faults
77