Page 1
Installation, operating and maintenance Instructions BNE 1 - BNE 2 - BNE 3 EN • 1 664Y1200.B...
Page 2
INDEX INTRODUCTION Who should read these instructions Symbols Applicable standards Important notes USER GUIDE Use of the boiler Burner shutdown DESCRIPTION General description Operating principle Design characteristics Boiler views and key to parts TECHNICAL CHARACTERISTICS General Operating condition limits Dimensions Domestic hot water performance General characteristics INSTALLATION...
The product must be installed and serviced by qualified engineers in accordance with the regulations in force. ACV declines all liability for any damage caused as a result of installation or in the event of the use of appliances or accessories Danger of electrocution.
USER GUIDE USE OF THE BOILER To ensure that your system operates correctly, please 7. Thermostat-pressure gauge have it serviced annually by a qualified engineer; This gauge shows the temperature of the boiler and the pressure in servicing should be completed before the start of the the primary heating circuit.
USER GUIDE DESCRIPTION The water escaping from the safety valve can GENERAL DESCRIPTION be extremely hot and cause serious burns. • Combined boiler and water heater (heating and domestic hot water) • Hot water generated by an indirect storage system. •...
DESCRIPTION Casing BOILER VIEWS AND KEY TO PARTS The boiler is covered with a steel casing that has been stove enamelled at 220°C after scouring and phosphating. 1. Cold water inlet 2. Hot water thermostat pocket 3. Hot water outlet Storage exchanger 4.
Page 7
TECHNICAL CHARACTERISTICS GENERAL OPERATING CONDITION LIMITS The appliances are supplied fully assembled, tested and packed Maximum service pressure (tank filled with water) standing on a timber transport base with impact protection strips - Heating circuit: 3 bar and wrapped in heat-shrunk plastic film. When the appliance arrives, - Hot water circuit: 10 bar remove the packaging and check that no parts have been damaged in transit.
INSTALLATION BOILER ROOM A. High-level ventilation B. Low-level ventilation C. Draught stabiliser Important D. Flame inspection window • Never obstruct the ventilation. E. Height of lined chimney • Do not store inflammable products in the boiler room. F. Chimney diameter •...
This kit comprises: Safety group • A pump; The safety group of the water tank must be approved by ACV and • A 3-way manual valve. This calibrated to 7 bar; the group’s valve discharge must be connected valve can be power-operated to the drain.
INSTALLATION ELECTRICAL CONNECTIONS Wiring diagram key 1. Main switch Power supply principle 2. Hot water control thermostat The boiler operates on a single-phase supply of 230 V/50 Hz. 3. Time clock You should install a control box with main switch and 6A fuses 4.
BURNER CHARACTERISTICS DESCRIPTION OF THE BURNER Advantages • Simple to install, it is fitted with a safety switch and a new burner suspension system. This new generation of fuel oil burners comply with current • A special key is provided with the burner for any maintenance requirements in terms of performance and the cleanliness of work needed.
COMMISSIONING AND MAINTENANCE FILLING THE DOMESTIC HOT WATER AND HEATING CIRCUITS IMPORTANT It is essential to fill the domestic hot water circuit before the heating circuit. 1. Open valves 7 and 8 to fill the domestic hot water circuit and pressurise it.
COMMISSIONING AND MAINTENANCE MAINTENANCE OF SAFETY EQUIPMENT - Check that all thermostats and safety devicesoperate correctly: the boiler thermostat and the manual reset high-limit thermostat (103°C). - Check the heating circuit safety valves. DRAINING THE BOILER The water draining from the drain cock is very hot and can cause serious burns.
Need help?
Do you have a question about the BNE Series and is the answer not in the manual?
Questions and answers