delta
pro & pro pack
Installation, operating and
maintenance instructions
EN • 1
664Y4300.E

Advertisement

Table of Contents
loading

Summary of Contents for ACV delta pro

  • Page 1 delta pro & pro pack Installation, operating and maintenance instructions EN • 1 664Y4300.E...
  • Page 2: Table Of Contents

    Dimensions installation Boiler room Optional balanced flue connection kit B23 flue connection Type of flue connection Flue connection accessories Domestic hot water connection Heating connection ACV BMV burner oil supply ACV BG 2000-S burner gas supply EN • 2 664Y4300.E...
  • Page 3: Who Should Read These Instructions

    • Defective parts can only be replaced with original factory parts. You will find a list of spare parts and their ACV reference number at the end of this manual. • BG 2000-S gas burners are pre-adjusted in the factory for natural gas [equivalent to G20].
  • Page 4: Description

    The different DElTA Pro models include, depending on their power, 4 or 8 The Delta Pro has a major advantage over other hot water boilers: it heats hot steel flue tubes with an internal diameter of 64 mm. Each tube is equipped...
  • Page 5 DEsCrIptIoN Delta Pro 25/45/55 models Delta Pro Pack 25/45 models 17 17 17 1 1 1 16 16 16 15 15 15 6 6 6 2 2 2 19 19 19 7 7 7 8 8 8 3 3 3...
  • Page 6: User Guide

    The heating circuit pressure must be at least 1 bar and must be regularly 5 - ACV controller (optional) checked by the end user. Always make sure that the appliance is off when refilling the system. To do this, use the ON/OFF switch. For further information, Refer to the controller instructions if you have this option.
  • Page 7: Oil Or Gas Burner Lockout

    In normal operation, the burner starts automatically as soon as the boiler drops below the temperature setpoint. ACV BMV1 (FV) & BMV2 (FV) oil burners To make sure your system works correctly, please have it serviced every year by a qualified technician before the heating season.
  • Page 8: Technical Characteristics

    - Maximum temperature: 90°C 4x Ø 6,5 (M8) wATEr quAlITY • Chlorides: < 150 mg/l • 6 ≤ ph ≤ 8 delta pro & delta pro & GEnEral charactEristics pro pack 25 pro pack 45 delta pro 55 Input power [Input]...
  • Page 9: Dimensions

    45 1760 1386 1445 1445 1400 — delta pro 55 1760 1586 1645 1645 1600 — delta pro pack 25 1760 1386 1723 1445 — 1400 delta pro pack 45 1760 1386 1723 1445 — 1400 (*) Empty weight without burner...
  • Page 10: Installation

    Given that regulations vary from one country to the next, these tables are given for information only. Delta Pro balanced flue (code: 10800194) Available only for Delta Pro & Pro Pack 25/45 models. Each installer must ensure that boiler room ventilation complies with current regulations.
  • Page 11: Type Of Flue Connection

    [Only if close enough together to be subjected to similar wind conditions. the boiler has an ACV BG 2000-S premix burner]. : Connection by pipes with vertical terminals that simultaneously take...
  • Page 12 INstaLLatIoN Flue connection options B23P EN • 12 664Y4300.E...
  • Page 13: Flue Connection Accessories

    INstaLLatIoN fluE connEction accEssoriEs Concentric Stainless steel - Stainless steel Ø 100/150 mm tErmInAlS code item siZE 537D6197 Vertical terminal 1515 mm 537D6198 Horizontal terminal with wall plates 795 mm DUCtS code item siZE 537D6199 Length 250 mm 210 mm 537D6200 Length 500 mm 460 mm...
  • Page 14: Domestic Hot Water Connection

    Expansion tank If there is a risk of low pressure in the hot water circuit (installation of a Delta Pro & Pro Pack on the roof of a building), it is essential to install a vacuum breaker device onto the cold water supply.
  • Page 15: Heating Connection

    The safety valves must be connected to the drain. DElTA PrO PACk hYDrAulIC kIT This hydraulic kit is factory assembled on Delta Pro Pack 25 and Delta Pro Pack 45 models comprising: • A circulator with automatic air eliminator built in.
  • Page 16 Supply construction and installation must be in accordance with current regulations. - The Delta Pro & Pro Pack boilers combined with an ACV BG 2000-S burner The oil pipe must be brought sufficiently close to the burner so that the hoses have a Ø...
  • Page 17: Electrical Connection

    ELECtrICaL CoNNECtIoN ElEctrical connEction The power to the boiler must be isolated before any work is SuPPlY PrINCIPlE carried out on it. The boiler uses a single phase supply at 230 V - 50 Hz. A mains isolator with 6A mcb (5A fuse) must be fitted outside the boiler to allow the power to be shut off during servicing and before any repairs are carried out.
  • Page 18: Unit

    CoNtroL installation of a hiGh or loW hEatinG circuit With control unit SChEMATIC DIAGrAM The heating (high temperature or floor heating) is controlled by the AF200 outside temperature detector supplied with the Control Unit and by the RFF room detector or RS Zone Unit. The detectors are connected to a controller that can be built into the boiler.
  • Page 19 CoNtroL wiring diagram for the intermediate base for connection to the Control unit 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 Bus B Bus A 15 16 17...
  • Page 20: Bmv Oil Burner Features

    BMV oil BurnEr For our DElTA Pro & Pro Pack boilers, we have opted for the latest technology of ACV BMV1 and BMV2 boilers, which involves a third-generation transparent flame burner. The advantages of this burner construction lie in operation saving the maximum amount of energy with very low emissions of harmful substances (approval according to EN 267:1999-11, category 3, the German ‘Blue Angel’...
  • Page 21: Bg 2000-S Gas Burner Features

    BG 2000-s Gas BUrNEr fEatUrEs acV BG 2000-s prEMix Gas BurnEr Air/gas mix control principle The BG 2000-S air/gas premix burner has a Honeywell gas valve, a venturi A. Air tube and an electric control relay. The gas valve has been specially designed for low NOx air/gas premix burners with automatic ignition and ionisation B.
  • Page 22: Gas Categories

    BG 2000-s Gas BUrNEr fEatUrEs Gas catEGoriEs i2E(s)B ii2h3B/p ii2h3p ii2E3B/p ii2Er3p ii2l3B/p ii2l3p 20 mbar 20 mbar 20 mbar 20 mbar 20 mbar 25 mbar 25 mbar 25 mbar 25 mbar 30 - 50 mbar 30 - 50 mbar 30 - 50 mbar 30 - 50 mbar 37 - 50 mbar 30 - 50 mbar 37 - 50 mbar 30 - 50 mbar 37 - 50 mbar 37 mbar...
  • Page 23 BG 2000-s Gas BUrNEr fEatUrEs Burner chamber plate Burner tube Ignition cable Flame sight glass Ionisation cable Control relay Potentiometer adjustment Burner power plug Ignition electrode Gas valve Burner rESET Ionisation electrode Gas connection Ø 3/4” [female] Burner chamber plate insulation Burner chamber plate seal Venturi tube EN •...
  • Page 24: Commissioning And Maintenance

    ACV advises that boilers should be serviced at least once a year. This service and any boiler inspections must be carried out by a qualified technician. water flowing out of the safety valve or the safety unit may be extremely hot and could cause severe burns.
  • Page 25 CommIssIoNING aND maINtENaNCE EN • 25 664Y4300.E...
  • Page 26 EN • 26 664Y4300.E...
  • Page 27 DElTA pRo & pRo pAcK 25 - 45 - 55 54322000 54764009 54441008 54766016 54442045 54764021 54766017 Ml • 1 664Y4300.E...
  • Page 28 DElTA pRo & pRo pAcK 25 - 45 21475455 21471455 21479455 21478455 21477455 21473455 21471455 21474455 21476455 Ml • 2 664Y4300.E...
  • Page 29 DElTA pRo 55 21475457 21471455 21479457 21477455 21473457 21471455 21474455 21476455 Ml • 3 664Y4300.E...
  • Page 30 DElTA pRo 25 - 45 557a1500 63438001 507f3049 557a5005 557a0016 55426017 49410045 507f2005 63438001 55426001 2147p455 51401049 51305000 50423365 Ml • 4 664Y4300.E...
  • Page 31 DElTA pRo 55 557a1500 63438001 507f3049 557a0016 557a5005 55426017 507f2009 49410039 16 x 507f2010 63438001 55426001 2147p455 51401049 51305000 50423365 Ml • 5 664Y4300.E...
  • Page 32 DElTA pRo pAcK 25 - 45 507f3049 63438001 557a0016 49410045 507f2005 63438001 2147p455 51401049 51305000 50423365 Ml • 6 664Y4300.E...
  • Page 33 DElTA pRo pAcK 25 - 45 557a1500 10800191 557a7007 557a5005 55426017 557a7008 55426001 Ml • 7 664Y4300.E...
  • Page 34 Ml • 8 664Y4300.E...
  • Page 35 Ml • 9 664Y4300.E...
  • Page 36 Ml • 10 664Y4300.E...

Table of Contents