8.5
Error messages
8.5.1
No floor sensor connected
Fig. 26:
No floor sensor connected
For the applications "Floor controlling" and "Room controlling / floor limitation" a floor sensor
must be connected.
If there is no floor sensor connected and one of the applications activated, the message "Sensor
floor error" will be displayed instead of the main menu.
–
The buttons have no function.
–
The controller carries out PWM control with 30% on-time heating.
To reset the error message, switch to the expert settings and select the application "Room
controlling", see chapter 8.4.3 "Expert menu ‒ Special functions" on page 31.
Product manual 2CKA001473B9664 │ 01.03.2020
Operation
│33