NFN Gateway Overview

1.4 Agency Listings

NOTE: ONYXWorks
requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864
9th Edition, as well as products that have not received UL 864 9th Edition certification. Operation
of a UL 864 9th Edition compliant system together with products not tested for UL 864 9th Edition
has not been UL evaluated. Such operation requires the approval of the local Authority Having
Jurisdiction (AHJ).
This product is intended to be installed in accordance with the Local Authority Having Jurisdiction
(LAHJ) and has been investigated to, and found to be in compliance with the following standards
and documents. Before proceeding, the installer should be familiar with them too.
Underwriters Laboratories U.S. Documents
UL-294: Access Control System Units, Fifth Edition.
UL-864: Control Units for Fire Protective Signaling Systems, Ninth Edition.
UL-1076: Proprietary Burglar Alarm Units and Systems, Fifth Edition.
Underwriters Laboratories Canada Documents
CAN/ULC-S527-99: Standard for Control Units for Fire Alarm Systems.
National Fire Protection Association Standards
NFPA 70: National Electrical Code.
NFPA 72: Installation, Maintenance, and Use of Protective Signaling Systems.
WARNING: Installation
!
Improper installation, maintenance, and lack of routine testing could result in system malfunction.
1.4.1 Environmental Requirements
This product must be installed in the following environmental conditions:
Temperature range of 0°C to 49°C (32°F - 120°F).
93% humidity non-condensing at 30°C (86°F).
14
®
systems work with products that have been certified to comply with the
NFN Gateway Installation & Operation Manual - P/N: 52306:Rev: D 06/01/07
Agency Listings